Главная страница | Регуляторы мощности | Thyro-A
Thyro-A
Thyristor Power Controller (SCR) up to 1,500 A
Safe, fast, economical and communication enabled
Owing to high-capacity digital technology, the new
communication enabled Thyristor Power Controller Thyro-A allows for precise
energy dosing at a high level of availability.
Heating Melting Forming
Highly flexible for interfacing the load and power supply
side, the range of applications for Thyro-A has expanded signifi cantly. For standard processes, adjustments can be made on the unit, which facilitate
handling and speed up commissioning.
Owing to an interface option at the automation level, many further functions can also be used. All measurement, status, and set points may be processed via SPS or the process computer. Of course, stand-alone operations
or the direct combination with process controls are still possible.
Thyro-A power controllers are thus excellently suited for application in numerous fields within the scope of process engineering
technology, for example:
- Ovens (industrial, diffusion, drying)
- Glass processing (plate glass equipment, feeders, finishing equipment,
fiber glass)
- Plant equipment (extruders, plastic presses)
- Chemical industry (pipe trace heaters, pre-heating equipment),
- Automotive industry (paint drying equipment),
- Printing machines (IR drying),
- Packaging industry (shrink tunnels)
Брошюра Thyro-A
Листовка Thyro-A
Инструкция по эксплуатации Thyro-A
|
Specification
Key Features
Besides free-from-wear operations and high performance, this
product series offers the following features:
- Simple handling requiring little space
- Rated voltages up to 600 V
- Rated currents up to 1,500 A
- Single, dual, and three-phase versions (Dual-phase version for three-phase
load without deploying the neutral conductor in a cost-saving three-phase
circuit)
- Integrated semi-conductor fuses
- LED status indicators
Automation Level
- Series-design system interface for connection to an optional bus module
(Profi bus DPV1, Modbus RTU, DeviceNet, CANopen, Profi Net. Projected: ModBus
TCP/IP, Ethernet IP) for the processing of set points and actual values, as
well as for status reports
- Interface option for connection to PC software Thyro-Tool Family
- Safe separation of control and power units
Analog Controlling
- Analog set point between 0..10V / 0..20mA
- Control characteristic is adjustable within this interval
- Voltage range at the dual point controller: OFF=0..3V, ON=3..24V
Load Side
- High resistance against short-circuit currents and blocking voltage
accommodated by the power semiconductors
- Designed for ohmic load, as well as for inductive mixed load
- Fit for transformer-type load due to an integrated soft-start function,
phase-angle firing of the first half-wave and channel separation
- Optimized load control due to the implementation of up to 5 control types
and 3 operating modes
Power Supply Side
- Network voltages of up to 0.43 x Unom
- Frequency range 47-63 Hz
- Internal network load optimization in the operating modes TAKT and QTM
- Optional external network load optimization (Thyro-Power Manager
Module)
Other Features
- Quality standard met in accordance with ISO 9001
- Approval in accordance with UL 508
- S.C.C.R. certified in accordance with UL 508A (100 kA short-circuit test,
accredited 16 A to 350 A, projected 495 A to 1,500 A)
- Canadian National Standard
- CE Conformity
- GOST
- RoHS Conformity 5/6
|
Наверх
Specification
Thyro-Power Manager

Thyro-Tool Family

|
Наверх
Specification – type series and technical data (excerpt)
Operating Modes
|
TAKT, full frequency package control
|
frequency package control
|
|
VAR, phase-angle
|
firing of each sinus half-wave
|
|
QTM, half-wave frequency package control
|
quick operating mode for ohmic load without a transformer
|
Thyro-A
|
1A...
|
single-phase version, for single-phase load between dual phases, or for a
single phase connected to the neutral phase
|
|
|
Operating modes:
|
TAKT, VAR, QTM
|
|
2A...
|
dual-phase version for three-phase load in cost-saving three-phase
circuit
|
|
|
Operating mode:
|
TAKT
|
|
3A...
|
three-phase version, for three-phase load
|
|
|
Operating modes:
|
TAKT, VAR
|
Rated Voltage ...H1
|
...230... 230 V - 57 % + 10 %
|
|
...400... 400 V - 57 % + 10 %
|
|
...500... 500 V - 57 % + 10 %
|
Rated Voltage ...H RL1 and H RLP1
|
...230... 230 V - 15 % + 10 %
|
230 V - 57 % together with 24 V input
|
|
...400... 400 V - 15 % + 10 %
|
400 V - 57 % together with 24 V input
|
|
...500... 500 V - 15 % + 10 %
|
500 V - 57 % together with 24 V input
|
|
...600... 600 V - 15 % + 10 %
|
600 V - 57 % together with 24 V input
|
|
Network frequency
|
of all types ranging from 47 Hz to 63 Hz
Max. frequency change 5 % per half-wave
|
Rated Current
|
...-xxx...
|
16 A, 30 A, 45 A, 60 A, 100 A, 130 A, 170 A, 280 A, 350 A, 495 A, 650 A,
1.000 A, 1.400 A, 1.500 A
|
|
Load Type
|
Load types for ohmic load employed at a Rwarm/Rcold
ratio of up to 6; Transformerload
|
|
Network load
|
optimization via internal network load optimization for the operating modes
QTM and TAKT
Interface for external network load optimization available, e.g. Thyro-Power
Manager
|
Functional Features
|
...F...
|
forced ventilation
|
|
|
Setpoint inputs
|
2 setpoint inputs, separated safely (SELV, PELV) from the mains
|
|
|
|
Input of analog setpoint, signal intervals:
|
|
|
|
0(4) - 20 mA / 0(1) - 5 V / 0(2) - 10 V
|
|
|
|
Control input for switch operation mode – dual-point control is possible
(UOn = 3-24 V)
|
|
|
|
The digital setpoint is provided by the process computer or bus system
|
|
...H 1
|
control types
|
Ueff, U2eff
|
|
...H RL1
|
functional features
|
such as ...H 1, yet additionally
|
|
|
Control types
|
Ueff, U2eff, Ieff,
I2eff
|
|
|
Load monitoring
|
via an adjustable response threshold
|
|
|
Limitations
|
current limitation Ieff, Î in VAR mode, current peak limitation
to Î = 3 x Inom
|
|
|
Relay output
|
exchanger, max. contact load 250 V, 6 A, 180 W, 1500 VA
|
|
|
Analog output
|
signal level 0(2)-10 Volt / 0(4)-20 mA, maximum compliance voltage 10 V, can
also be used as adjustment aid
|
|
|
external supply
|
24 V DC/AC, connected only upon demand
|
|
|
Load types
|
for ohmic load employed at a Rwarm/Rcold ratio of up
to 6 (only deployed for H RL1 and H RLP)
|
|
|
|
Limitation to Î = 3 x Inom (for H RL1 and H RLP in VAR mode)
|
|
|
Operational display
|
via LEDs and relay outputs (exchanger, indications adjustable)
|
|
...H RLP1
|
functional features
|
such as ... H RL1, however, additionally
|
|
|
control types
|
Ueff, U2eff, Ieff,
I2eff, P
|
System interface
|
Optional bus module for Profibus DPV1, Modbus RTU, DeviceNet, CANopen,
ProfiNet.
Projected: ModBus TCP/IP, Ethernet IP.
|
|
For interfacing the PC software of the Thyro-Tool Family via a PC
adaptor
|
Examples regarding the type key
|
Thyro-A 2A 400-170 HRLP1
|
|
2A = dual phase version for three phase load in cost-saving three-phase
circuit, 400 = 400 V rated voltage
|
|
170 = 170 A rated current, H = semi-conductor fuse, R = failure indicator
relay
|
|
L = load monitoring + analog output, P = performance control display, 1 =
actual series
|
|
Наверх
Specification - type series and technical data (excerpt)
THYRO-A 1A
H1(*), HRL1, HRLP1
|
Single-phase power controller
|
|
Current
|
Unit rating (kVA)
|
Power loss
|
Dimensions (mm)
|
Weight (kg)
|

|
…H1 …HRL1 …HRLP1
|
(A)
|
230 V
|
400 V
|
500 V
|
600 V
|
(W)
|
W
|
H
|
D
|
approx.
|
|
16
|
3.7
|
6.4
|
8
|
—
|
30
|
45
|
131
|
127
|
0.7
|
|
30
|
6.9
|
12
|
15
|
—
|
47
|
45
|
131
|
127
|
0.7
|
|
45
|
10
|
18
|
22.5
|
—
|
48
|
52
|
190
|
182
|
1.7
|
|
60
|
14
|
24
|
30
|
—
|
80
|
52
|
190
|
182
|
1.7
|
|
100
|
23
|
40
|
50
|
—
|
105
|
75
|
190
|
190
|
1.9
|
|
130
|
30
|
52
|
65
|
—
|
150
|
125
|
320
|
237
|
4
|
|
170
|
39
|
68
|
85
|
—
|
210
|
125
|
320
|
237
|
4
|
..F..
|
280
|
64
|
112
|
140
|
—
|
330
|
125
|
370
|
237
|
5
|
..F..
|
350
|
80
|
140
|
175
|
—
|
390
|
125
|
400
|
261
|
8.4
|
..F..
|
495
|
—
|
198
|
274
|
297
|
556
|
112
|
414
|
345
|
15
|
..F..
|
650
|
—
|
260
|
325
|
390
|
638
|
112
|
414
|
345
|
15
|
..F..
|
1000
|
—
|
400
|
500
|
600
|
1277
|
239
|
729
|
516
|
35
|
..F..
|
1400
|
—
|
—
|
750
|
900
|
1700
|
239
|
729
|
516
|
35
|
..F..
|
1500
|
—
|
600
|
—
|
—
|
1703
|
239
|
729
|
516
|
35
|
THYRO-A 2A
H1(*), HRL1, HRLP1
|
Dual-phase power controller for three-phase loads implement with
cost-saving three-phase circuit configuration
|
|
Current
|
Unit rating (kVA)
|
Power loss
|
Dimensions (mm)
|
Weight (kg)
|

|
…H1 …HRL1 …HRLP1
|
(A)
|
230 V
|
400 V
|
500 V
|
600 V
|
(W)
|
W
|
H
|
D
|
approx.
|
|
16
|
—
|
11
|
14
|
—
|
60
|
90
|
131
|
127
|
1.4
|
|
30
|
—
|
21
|
26
|
—
|
94
|
90
|
131
|
127
|
1.4
|
|
45
|
—
|
31
|
39
|
—
|
96
|
104
|
190
|
182
|
3.4
|
|
60
|
—
|
42
|
52
|
—
|
160
|
104
|
190
|
182
|
3.4
|
|
100
|
—
|
69
|
87
|
—
|
210
|
150
|
190
|
190
|
3.8
|
|
130
|
—
|
90
|
112
|
—
|
300
|
250
|
320
|
237
|
8
|
|
170
|
—
|
118
|
147
|
—
|
420
|
250
|
320
|
237
|
8
|
..F..
|
280
|
—
|
194
|
242
|
—
|
660
|
250
|
393
|
237
|
11
|
..F..
|
350
|
—
|
242
|
303
|
—
|
780
|
250
|
430
|
261
|
16.7
|
..F..
|
495
|
—
|
343
|
429
|
514
|
1190
|
194
|
380
|
345
|
22
|
..F..
|
650
|
—
|
450
|
563
|
675
|
1465
|
194
|
380
|
345
|
22
|
..F..
|
1000
|
—
|
693
|
866
|
1039
|
2785
|
417
|
685
|
516
|
54
|
..F..
|
1400
|
—
|
—
|
1299
|
1599
|
3300
|
417
|
685
|
516
|
54
|
..F..
|
1500
|
—
|
1039
|
—
|
—
|
3510
|
417
|
685
|
516
|
54
|
THYRO-A 3A
H1(*), HRL1, HRLP1
|
Three-phase power controller
|
|
Current
|
Unit rating (kVA)
|
Power loss
|
Dimensions (mm)
|
Weight (kg)
|

(*) …H1 types available up to 350 A
|
…H1 …HRL1 …HRLP1
|
(A)
|
230 V
|
400 V
|
500 V
|
600 V
|
(W)
|
W
|
H
|
D
|
approx.
|
|
16
|
—
|
11
|
14
|
—
|
90
|
135
|
132
|
127
|
2.1
|
|
30
|
—
|
21
|
26
|
—
|
141
|
135
|
132
|
127
|
2.1
|
|
45
|
—
|
31
|
39
|
—
|
144
|
156
|
190
|
182
|
5.1
|
|
60
|
—
|
42
|
52
|
—
|
240
|
156
|
190
|
182
|
5.1
|
|
100
|
—
|
69
|
87
|
—
|
315
|
225
|
190
|
190
|
5.7
|
|
130
|
—
|
90
|
112
|
—
|
450
|
375
|
320
|
241
|
12
|
|
170
|
—
|
118
|
147
|
—
|
630
|
375
|
320
|
241
|
12
|
..F..
|
280
|
—
|
194
|
242
|
—
|
990
|
375
|
397
|
241
|
15
|
..F..
|
350
|
—
|
242
|
303
|
—
|
1170
|
375
|
430
|
261
|
25.5
|
..F..
|
495
|
—
|
343
|
429
|
514
|
1860
|
276
|
407
|
345
|
30
|
..F..
|
650
|
—
|
450
|
563
|
675
|
2265
|
276
|
407
|
345
|
30
|
..F..
|
1000
|
—
|
693
|
866
|
1039
|
4310
|
583
|
685
|
516
|
74
|
..F..
|
1400
|
—
|
—
|
1299
|
1559
|
5000
|
583
|
685
|
516
|
74
|
..F..
|
1500
|
—
|
1039
|
—
|
—
|
5325
|
583
|
685
|
516
|
74
|
|
Наверх
|